Please use this identifier to cite or link to this item:
http://hdl.handle.net/10773/17473
Title: | Avaliação energética de um edifício de serviços: Escola Superior Aveiro Norte |
Author: | Ramalho, José Carlos Martins |
Advisor: | Martins, Nelson Amadeu Dias |
Keywords: | Piso radiante Edifícios - Climatização Eficiência energética Escola Superior Aveiro Norte |
Defense Date: | 2016 |
Publisher: | Universidade de Aveiro |
Abstract: | O objetivo principal deste trabalho é realizar uma avaliação energética à Escola
Superior Aveiro Norte (ESAN), que é um polo da Universidade de Aveiro, situado
em Oliveira de Azeméis. A motivação na escolha do objeto de estudo deste
trabalho prende-se com o facto de ser um edifício único, recente, com pouco
estudadas em Portugal, como bombas de calor geotérmicas associadas a piso
radiante e ventilação, com pré-aquecimento de ar com recurso a painéis solares
e recuperação de calor. Estas tecnologias foram usadas com vista a obter
conforto, com um baixo consumo energético, apesar de não estarem a conseguir
garantir essas condições. Por outro lado, o interesse no edifício está no facto de
não ter sido, até à data, objeto de estudos relativos ao desempenho energético,
desde a sua construção.
Para realizar o estudo, utilizou-se o programa de simulação dinâmica
DesignBuilder para modelar o edifício, introduzindo-se os dados relativos à
envolvente, iluminação, ocupação, equipamentos e sistemas de climatização.
A partir da análise dos resultados e do conhecimento do edifício proveniente do
estudo da documentação fornecida e das visitas ao local, foi possível verificar
que a heterogeneidade da área de envidraçados e das cargas térmicas entre as
diferentes salas conjugada com a climatização pelos mesmos sistemas, causa
grandes desequilíbrios térmicos e dificuldades no controlo das condições de
conforto dentro do edifício.
Consequentemente, propõem-se medidas corretivas com vista a melhorar o
conforto térmico e a eficiência energética, sendo algumas delas de baixo custo
de implementação e poupanças energéticas significativas. Essas medidas têm
vista a corrigir problemas de âmbito da implementação e controlo dos sistemas
de climatização, ao nível do controlo da iluminação, da localização dos painéis
solares para produção de Água Quente Sanitária, do aumento do isolamento da
laje de betão que contém o piso radiante e da proteção solar pelo exterior da
área envidraçada. The main goal of this project is to carry out an energy assessment to the School of Design, Management and Production Technologies Northern Aveiro (Escola Superior Aveiro Norte - ESAN), which is a the most recent organic unit of the University of Aveiro, located in the town of Oliveira de Azeméis. The motivation in choosing this subject relates to the fact that it is a unique, new building, modern with not very studied technologies, such Ground Source Heat Pumps associantd with radiant floors and ventilation with air preheating, aided by solar air panels and sensible heat recuperation. These technologies were used to achieve comfort, with a low energy consumption, even though they were not able to guarantee these conditions. Furthermore, the interest in the building is the fact that it is has not been, to date, the object of any study concerning energy performance, since its construction. For this study, it was used DesignBuilder a dynamic simulation program for modeling the building, entering data on the environment, lighting, occupancy, equipment and HVAC systems. From the analysis of the results and knowledge of the building from the study of the documentation provided and the site visits, it was possible to verify that the heterogeneity of the area of glazing and of the thermal loads between the different rooms combined with the HVAC through the same systems causes great thermal imbalances and difficulties in controlling the comfort conditions inside the building. Consequently, corrective measures are proposed to improve thermal comfort and energy efficiency, some of them with low implementation costs and significant energy savings. These measures are aimed at correcting problems related to the implementation and control of HVAC systems, in terms of lighting control, the location of solar panels for the production of Sanitary Hot Water, increasing the insulation of the concrete slab containing radiant floor and solar protection by the exterior of the glazed area. |
Description: | Mestrado em Engenharia Mecânica |
URI: | http://hdl.handle.net/10773/17473 |
Appears in Collections: | UA - Dissertações de mestrado DEM - Dissertações de mestrado |